8-29
IM 05P01C31-01EN
Control Functions
n
CascadePositionProportionalControlFunctionBlockDiagram
Communication
Target setpoints 1 to 8
COM
Aux. input
*1
LOCALREMOTE
SP ramp rate
SP limiter
Loop-1 PV input
Equipped as standard
Loop-2 PV input
DI2 DI3DI1 DI16PV RSP
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias
PV input filter
Ratio bias computation
Contact inputs
A.BS
A.FL
BS
FL
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
10-seg. linearizer approx./bias
PV input bias
PV input filter
BS
FL
PMD An, Bn
CNT ALG
UPR, DNR TMU
SPNO
SPNO
SP
R/L
RMS
SPH, SPL
UPR, DNR
C/A/M
SPH, SPL
RFL
A.SR A.LC
UNIT
IN
RH, RL
SDP
SH, SL
A.BS
A.FL
A.SR A.LC
UNIT
IN
RH, RL
SDP
SH, SL
AIN2
PMD An, Bn
A.BS
A.FL
A.SR A.LC
UNIT
IN
RH, RL
SDP
SH, SL
Tracking signal (Tracking when not in Cascade)
AUTO, MAN
AUTO, MAN
CAS
CAS
Switch to AUTO when
Loop-1 PV input burnout
or A/D error occurs.
Loop-2 target setpoints
OH, OL
SP ramp rate
SP limiter
RUNSTOP
S/R
Remote input filter
Output limiter
STOP (ON)/RUN (OFF) switch
STOP (ON)/RUN (OFF) switch
Loop-1 control computation
Manual operation
Input error preset output
Preset output
When Loop-2 sensor
burnout
occurs
Normal
MAN
RUNSTOP
EPO
OH, OL
PO
C/A/M
S/R
CAS, AUTO
A/M
Output limiter
Signal comparison
Feedback input
Direct/reverse signal
Motor-operated valve
Relay output
VALV
FBIN
M
Equipped as standardEquipped as standard Equipped as standard
Current
LPS
24 V loop
power supply
Current
OUT RET AL3AL2AL1
PMD
OU.H OU.L
HYS
DB
An, Bn
Split computation
10-seg. linearizer approx./bias
RET.H RET.L
PMD An, Bn
Split computation
10-seg. linearizer approx./bias
OUT retransmission output
O1RS
RET retransmission output
RTS
Alarm
Valve position sliding
resistor or current
In Estimating-type position proportional control, the limiter function
does not work on output operation.
The reverse-signal relay turns on when being limited by low limit.
The direct-signal relay turns on when being limited by high limit.
H relay
( key)
L relay
( key)
In Manual operation, the relay turns on while the or key is pressed.
Output limiter does not work.
For the model with optional suffix code /DR:
Remote input with direct input (E1-terminal area)
can be used when
UT55A suffix code: Type 2 = 1, 2, 4, 5, or 7 and
with optional suffix code /DR;
UT52A suffix code: Type 2 = 1 or 2 and
with optional suffix code /DR.
However, DI16 is to be deleted.
* The LP2 lamp is lit while the Loop-2 parameter is displayed.
Cascade (OFF→ON)
Automatic (OFF→ON)
Manual (OFF→ON)
STOP (ON)/RUN (OFF) switch
Loop-2 control computation
Alarm 1
(Loop-1 PV high limit)
Alarm 2
(Loop-1 PV low limit)
Alarm 3
(Loop-1 PV high limit)
Terminal Parameter Function
Analog signal Contact signal Front panel key
Legend
PV display
SP display
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
PV display
SP display
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Aux. analog (remote) input
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
Position Proportional Computation Output cannot be calculated by ladder program.
*
*
An external analog signal can
be used for Loop-2 SP. Use
the ladder program of LL50A
Parameter Setting Software
to build the function.
*1: RS-485, Ethernet, PROFIBUS-DP,
DeviceNet, CC-Link
**
**
**
**
**
**
**
**
Loop-2 parameters
Universal input (E1-terminal area) can be used
when UT55A/UT52A optional suffix code /U1.
However, DI16 does not exist.
(For Detailed model)
Remote input can be used when UT55A
optional suffix code /A2.
(For Standard model)
Remote input can be used when UT55A
suffix code: Type 2 = 7.
(For Detailed model) UT55A/UT52A
optional suffix code /R1
or /RCH1 is
necessary.
(For Standard model)
UT55A suffix
code: Type 2 = 1, 2, 4, 5, or 7; UT52A
suffix code: Type 2 = 1 or 2 is necessary.
(For Detailed model)
DI16 is equipped
when
UT55A/UT52A optional suffix code
/R1 or /RCH1.
(For Standard model)
DI16 is equipped
when UT55A suffix code: Type 2 = 1, 2, 4, 5,
or 7; UT52A suffix code: Type 2 = 1 or 2.
8
8.1SettingControlMode(CTLM)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UT55A and is the answer not in the manual?

YOKOGAWA UT55A Specifications

General IconGeneral
BrandYOKOGAWA
ModelUT55A
CategoryTemperature Controller
LanguageEnglish

Related product manuals