8-41
IM 05P01C31-01EN
Control Functions
n
LoopControlwithPVSwitchingFunctionBlockDiagram
Target setpoints 1 to 8
COM
Aux. input
Output limiter
Manual operation
Manual preset output
Input error preset output
Preset output
AUTO (ON)/MAN (OFF) switch
STOP (ON)/RUN (OFF) switch
LOCALREMOTE
AUTO
When sensor burnout occurs
Normal
MAN
RUNSTOP
SP ramp rate
SP limiter
PV input 1 PV input 2
DI16PV
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
Remote input filter
PV input bias
PV input filter
Ratio bias computation
PV switching
Contact inputs
Output limiter
A.BS
A.FL
BS
FL
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
PV.2C PV.HL PV.LL
P.UNI P.DP P.RH, P.RL
CNT ALG
UPR, DNR TMU
SPNO SP
R/L
RMS
SPH, SPL
RFL
A.SR A.LC
UNIT
IN
RH, RL
SDP
SH, SL
RSP
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
A.BS
A.FL
A.SR A.LC
UNIT
IN
RH, RL
SDP
SH, SL
PMD An, Bn
AIN2
A.BS
A.FL
A.SR A.LC
UNIT
IN
RH, RL
SDP
SH, SL
EPO
OH, OL
OH, OL OLMT
PO
S/R
MPON
Equipped as standard
OT
Equipped as standard Equipped as standard
Heater break alarm
HAL2HAL1
Heater break
alarm 1
Heater break
alarm 2
Current or
voltage pulse
Relay
LPS
24 V loop
power supply
Current
OUTOUT RET AL3AL2AL1
PMD
OU.H OU.L
An, Bn
Split computation
10-seg. linearizer approx./bias
RET.H RET.L
PMD An, Bn
Split computation
10-seg. linearizer approx./bias
OUT retransmission output
O1RS
RET retransmission output
RTS
* After the control output terminal is specified by the parameter OT,
other current output terminals can be used as retransmission output.
Alarm
Output terminal assignment
DI3DI1 DI2
A/M
Sensor burnout occurs when PV or RSP input burnout occurs.
However, burnout is not detected if input is not connected.
Control computation
RSP terminal input (ON)/PV terminal input (OFF) switch
(Current when retransmission output)
For the model with optional suffix code /DR:
Remote input with direct input (E1-terminal area)
can be used when
UT55A suffix code: Type 2 = 1, 2, 4, 5, or 7 and
with optional suffix code /DR;
UT52A suffix code: Type 2 = 1 or 2 and
with optional suffix code /DR.
However, DI16 is to be deleted.
No function
is assigned
to DI3.
Terminal Parameter Function
Analog signal Contact signal Front panel key
Legend
Alarm 1
(PV high limit)
Alarm 2
(PV low limit)
Alarm 3
(PV high limit)
Aux. analog (remote) input (E1-terminal area)
PV display
SP display
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Aux. analog (remote) input
10-seg. linearizer approx./bias
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
*1: RS-485, Ethernet, PROFIBUS-DP,
DeviceNet, CC-Link
Universal input (E1-terminal area) can be used
when UT55A/UT52A optional suffix code /U1.
However, DI16 does not exist.
(For Detailed model)
UT55A/UT52A optional suffix code /R1 or
/RCH1 is necessary.
(For Standard model)
UT55A suffix code: Type 2 = 1, 2, 4, 5, or 7;
UT52A suffix code: Type 2 = 1 or 2 is
necessary.
(For Detailed model)
Remote input can be used when
UT55A optional suffix code /A2.
(For Standard model)
Remote input can be used when
UT55A suffix code: Type 2 = 7.
(For Detailed model)
DI16 is equipped when UT55A/UT52A
optional suffix code /R1 or /RCH1.
(For Standard model)
DI16 is equipped when UT55A suffix
code: Type 2 = 1, 2, 4, 5, or 7; UT52A
suffix code: Type 2 = 1 or 2.
8
8.1SettingControlMode(CTLM)