EasyManua.ls Logo

YOKOGAWA UT55A - Page 355

YOKOGAWA UT55A
476 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16-4
IM 05P01C31-01EN
16.1.3 ErrorsduringOperation
ErrorsduringOperation(1)
The errors shown below may occur during operation.
PVdisplay
(Operation
Display)
Setpoint
display
(Operation
Display)
Status indicator
(Operation
Display)
Parameterthat
displays error details
Error description Cause and diagnosis Remedy
AD.ERR
Normal
indication
(Note)
Setup parameter
(AD1.E)
Analog input terminal ADC error
•PVinput
• RSP
input (E1-terminal area)
AIN2 input (E2-terminal area)
AIN4 input (E4-terminal area)
Analog input terminal AD value error
Faulty
Contact us for repair.
RJC.E
(Displays
RJC.E
andPV
alternately.)
Normal
indication
(Note)
Setup parameter
(AD1.E)
Universal input terminal RJC error
PVinput
• RSP
input (E1-terminal area)
Universal input terminal RJC error
Faulty
Contact us for repair.
Set the parameter RJC to OFF to erase
error indication.
B.OUT
Normal
indication
(Note)
Setup parameter
(AD1.E)
Analog input terminal burnout
error
PVinput
• RSP
input (E1- terminal area)
AIN2 input (E2-terminal area)
AIN4 input (E4-terminal area)
Analog input terminal sensor burnout
Check wiring and sensor.
Error indication is erased in normal
operation.
Setup parameter
(PV1.E/PV2.E)
PVinputburnout
error
(Loop1, Loop2)
Burnoutofanalog
inputconnectedtoPV
Check wiring and sensor of connected
analog input terminal.
Error indication is erased in normal
operation.
OVER
-OVER
Normal
indication
Setup parameter
(PV1.E/PV2.E)
PVinputover-scale
PV
inputunder-scale
(PVvaluesoutof-5to105%)
(Loop1, Loop 2)
PVinputis
outof-5to105%.Alsooccurs
when the data out of range which is the
ladder computation result is input.
Check analog input value or ladder
program.
Normal
indication
Normal
indication
Setup parameter
(PV1.E/PV2.E)
RSP input burnout error
(Loop 1, Loop 2)
Burnout of analog input connected to
RSP
Check wiring and sensor. Error indication
is erased in normal operation.
Note: When an error occurs in input shown in Analog input display (Operation display).
Setpoint
displayshowsthesamesymbolasthePVdisplay.
16.1Troubleshooting

Table of Contents

Related product manuals