17-12
IM 05P01C31-01EN
UT55A/UT52A
CurrentandVoltagePulseOutput
(ForStandardmodel)Standardtypeor
Heating/coolingtypeheating-sideoutput
(UT55A/UT52A)
(ForDetailedmodel)SufxcodeofOutput1
=“-A”or“-U”(UT55A/UT52A)
(ForStandardmodel)Heating/coolingtype
cooling-sideoutput(UT55A)
(ForDetailedmodel)SufxcodeofOutput2
=“A”or“U”(UT55A)
208
207
OUT
Shield
–
+
Control valves
(or other
actuators)
Current:
4 to 20 mA DC or 0 to 20 mA DC
(resistance load: 600 Ω or less)
Voltage pulse:
On-voltage: 12 V DC or more
(load resistance: 600 Ω or more)
Off-voltage: 0.1 V DC or less
Class D grounding
(grounding resistance of
100 Ω or less)
512
511
OUT2
Shield
–
+
Current:
4 to 20 mA DC or 0 to 20 mA DC
(resistance load: 600 Ω or less)
Voltage pulse:
On-voltage: 12 V DC or more
(load resistance: 600 Ω or more)
Off-voltage: 0.1 V DC or less
Class D grounding
(grounding resistance of
100 Ω or less)
Control valves
(or other
actuators)
(ForStandardmodel)Heating/coolingtype
cooling-sideoutput(UT52A)
(ForDetailedmodel)SufxcodeofOutput2
=“A”or“U”(UT52A)
312
311
OUT2
Shield
–
+
Current:
4 to 20 mA DC or 0 to 20 mA DC
(resistance load: 600 Ω or less)
Voltage pulse:
On-voltage: 12 V DC or more (load resistance: 600 Ω or more)
Off-voltage: 0.1 V DC or less
Class D grounding
(grounding resistance of
100 Ω or less)
Control valves
(or other
actuators)
Use
When current/voltage pulse output is not used for control output, it can be used for
retransmission output.
When retransmission output terminal is not used for retransmission output, it can be used
for optional control output. The current output range can be changed.
For control output setting, set the control mode (CTLM) and the control type (CNT), then
set the output terminal and output type in the output type selection (OT).
► Controloutputtype:10.1SettingControlOutputType
17.4 Wiring