18-41
IM 05P01C31-01EN
Parameters
18
I/ODisplayMenu(Menu:I/O)
Parameter
symbol
Name
Display
level
Read only
KEY Key status PRO
See Chapter 13.
X000 DI1-DI3 status (equipped as standard) PRO
X100 DI11-DI16 status (E1-terminal area) PRO
X200 DI21-DI26 status (E2-terminal area) PRO
X300 DI31-DI35 status (E3-terminal area) PRO
X400 DI41-DI46 status (E4-terminal area) PRO
Y000 AL1-AL3 status (equipped as standard) PRO
Y100 DO11-DO15 status (E1-terminal area) PRO
Y200 DO21-DO25 status (E2-terminal area) PRO
Y300 DO31-DO35 status (E3-terminal area) PRO
Y400 DO41-DO45 status (E4-terminal area) PRO
SystemSettingMenu(Menu:SYS)
Parameter
symbol
Name
Display
level
Setting range Initialvalue
R.MD Restart mode STD
CONT: Continue action set before
power failure.
MAN: Start from MAN.
AUTO: Start from AUTO.
CONT
R.TM Restart timer STD 0 to 10 s 0
EPO
Input error preset
output
STD
0: Preset output
1:0%output
2:
100%output
0
C.GRN
Response as
GREEN Series
PRO
OFF: Works as UT55A/UT52A
in communication of device
information response or
broadcasting.
ON: Works as GREEN Series
in communication of device
information response or
broadcasting.
OFF
FREQ Power frequency EASY AUTO,60:60Hz,50:50Hz AUTO
QSM Quicksettingmode EASY
OFF: Disable
ON: Enable
ON
LANG
Guide display
language
EASY
ENG: English
FRA: French
GER: German
SPA: Spanish
Depends on
the Model and
SufxCodes
PASS Password setting EASY
0 (No password) to 65535
Once a password is set, you can
no longer choose not to set a
password.
0
SMEC
Sampling period
error counter
PRO
0 to 65535 (display only)
0 when power
is turned on.
18.2ListofParameters