176 Program features
In the low voltage mode, the default voltage control and trip levels as well as the
brake chopper operation levels (see sections Voltage control and trip limits on page
161 and Brake chopper on page 161) are changed as follows:
Settings
Diagnostics
Level Value of parameter 47.04 BATTERY SUPPLY
FALSE TRUE
Supply voltage range 200…240 V AC ±10%
270…324 V DC ±10%
*48…270 V DC ±10%
Overvoltage trip level Unaffected Unaffected
Overvoltage control level 47.03 LOW VOLT DC MAX 47.03 LOW VOLT DC MAX
Undervoltage control level 47.02 LOW VOLT DC MIN Disabled
Undervoltage trip level 47.02 LOW VOLT DC MIN - 50 V Disabled
Brake chopper activation
level
47.03 LOW VOLT DC MAX - 30 V 47.03 LOW VOLT DC MAX - 30 V
Brake chopper maximum
power level
47.03 LOW VOLT DC MAX + 30 V 47.03 LOW VOLT DC MAX + 30 V
*Requires additional DC power supply JPO-01
Parameters Additional information
47.01 LOW VOLT MOD ENA Selects a signal source that enables/disables the low voltage mode.
47.02 LOW VOLT DC MIN Minimum DC voltage for the low voltage mode.
47.03 LOW VOLT DC MAX Maximum DC voltage for the low voltage mode.
47.04 BATTERY SUPPLY Selects a signal source that enables/disables external power unit supply,
used with low DC supply voltages such as a battery.
Signals Additional information
Alarms
LOW VOLT MOD CON Low voltage mode is activated but the parameter settings are outside
allowable limits.