226 Parameters
0b0000…0b1111 AI1/AI2 signal supervision selection. 1 = 1
15
15 ANALOGUE
OUTPUTS
Settings for the analogue outputs.
15.01 AO1 PTR
Selects a drive signal to be connected to analogue
output AO1.
See parameter 01.05 CURRENT PERC.
P.CURRENT
PERC / Val
pointer
Value pointer (See Terms and abbreviations on page
183.)
15.02 AO1 FILT TIME
Defines the filtering time constant for analogue
output AO1.
0.100 s/
Real
0.000…30.000 s Filter time constant for AO1. 1000 = 1 s / -
15.03 AO1 MAX
Defines the maximum value for analogue output
AO1.
20.000 mA/
Real
0.000…22.700
mA
Maximum AO1 output value. 1000 = 1 mA
/ -
15.04 AO1 MIN
Defines the minimum value for analogue output AO1. 4.000 mA/
Real
0.000…22.700
mA
Minimum AO1 output value. 1000 = 1 mA
/ -
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)
63
%
100
T
t
O = I × (1 - e
-t/T
)
I = filter input (step)
O = filter output
t = time
Unfiltered signal
Filtered signal