Parameters 229
16
16 SYSTEM
Local control and parameter access settings,
restoration of default parameter values and saving of
parameters into permanent memory.
16.01 LOCAL LOCK
Selects the source for disabling local control
(Take/Release button on the PC tool, LOC/REM key
of the panel). 1 = Local control disabled. 0 = Local
control enabled.
WARNING! Before activating, make sure
that the control panel is not needed for
stopping the drive.
C.False /
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
1 = 1
16.02 PARAMETER LOCK
Selects the state of the parameter lock. The lock
prevents parameter changing.
Note: This parameter can only be adjusted after the
correct pass code is entered at parameter 16.03
PASS CODE.
Open / enum
Locked Locked. Parameter values cannot be changed from
the control panel.
0
Open The lock is open. Parameter values can be changed. 1
Not saved The lock is open. Parameter values can be changed,
but the changes will not be stored at power switch
off.
2
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)