Parameters 283
99
99 START-UP
DATA
Start-up settings such as language, motor data and
motor control mode.
99.01 LANGUAGE
Selects the language.
Note: Not all languages listed below are necessarily
supported.
ENGLISH /
enum
ENGLISH English 0809 hex
DEUTSCH German 0407 hex
ITALIANO Italian 0410 hex
ESPAÑOL Spanish 040A hex
RUSSKI Russian 041D hex
TÜRKÇE Turkish 041F hex
99.02 MOTOR TYPE
Selects the motor type.
Note: This parameter cannot be changed while the
drive is running.
AM /
enum
AM Asynchronous motor. Three-phase AC voltage
supplied induction motor with a squirrel cage rotor.
0
PMSM Permanent magnet motor. Three-phase AC voltage
supplied synchronous motor with a permanent
magnet rotor and sinusoidal BackEMF voltage.
1
99.03 MOT NOM
CURRENT
Defines the nominal motor current. Must be equal to
the value on the motor rating plate. If several motors
are connected to the inverter, enter the total current
of the motors.
Note:
• Correct motor run requires that the magnetising
current of the motor does not exceed 90 percent of
the nominal current of the inverter.
• This parameter cannot be changed while the drive
is running.
- / Real
- Nominal motor current.
Note: The allowed range is 1/6…2 × I
2N
of drive.
- / 10 = 1 A
No. Bit/Name/Value/
Range
Description Def/Type
FbEq