Parameters 285
99.07 MOT NOM POWER
Defines the nominal motor power. Must be equal to
the value on the motor rating plate. If several motors
are connected to the inverter, enter the total power of
the motors. Set also parameter 99.08 MOT NOM
COSFII.
Note: This parameter cannot be changed while the
drive is running.
- / Real
0.00…
10000.00 kW
Nominal motor power. - /
100 = 1 kW
99.08 MOT NOM COSFII
Defines the cosphi (not applicable to permanent
magnet motors) for a more accurate motor model.
Not obligatory; if set, should be equal to the value on
the motor rating plate.
Note: This parameter cannot be changed while the
drive is running.
0.00 /
Real24
0.00…1.00
Cosphi (0 = parameter disabled). - / 100 = 1
99.09 MOT NOM
TORQUE
Defines the nominal motor shaft torque for a more
accurate motor model. Not obligatory.
Note: This parameter cannot be changed while the
drive is running.
0.000 N•m /
INT32
0.000…
2147483.647
N•m
Nominal motor shaft torque. - / 1000 =
1 N•m
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)