114 | PGC5000 GEN 2 | 892 J006 MNAH
Indicator
Issue
Resolution
Reset
Source
Invalid Analysis
Analysis failed validation
From Analysis Tab, edit Analysis to
meet requirements. User controlled.
AOC
Analysis
DigIn Check TCF
Programmable Input
checks.
See Digital input TCF.
AOC
Script
Prsr Check TCF
Pressure Check failed
See pressure check TCF.
AOC
Script
Offline
Schedule Offline: Oven is
powered down
Information Only. Resets when oven
power is restored.
AOC
Schedule
Idle
Schedule Stopped or
paused
Information Only.
AOC
Schedule
Calibrating
Schedule running an
analysis on Calibration
Stream
Information Only.
AOC
Schedule
Validating
Schedule running an
analysis on a Validation
Stream
Information Only.
AOC
Schedule
Maintenance
Schedule set in
Maintenance State
Information Only.
AOC
Schedule
Compile Error
Syntax errors in Script
From Program Tab check script syntax.
Next Run
Script
Runtime Error
Script encountered error
during execution
From Program Tab check script objects.
Next Run
Script
Script Not Found
Script specified in TCF
cannot be located
Ensure Script is in the Script library.
Next Run
Script
Missing Report
Script can’t find the
report to be modified
Edit the analysis under the Analysis
Tab. Script TCF must have a time
greater than the analysis cycle time.
Next Run
Script
Run Time
Exceeded
Script exceeded allotted
runtime
From Program Tab, check script logic,
increase Max Runtime variable.
Next Run
Script
User Error #1 - 10
Script Asserts Error
#1 - 10
User programmable indicators.
Information only.
Next Run
Script
Node Loss
Device no longer
reachable on SHS CAN
bus
Check cables and communication path
on SHS CANBus
AOC
SHS
New Node
Device added to SHS
CAN bus
Information Only
AOC
SHS
Address Conflict
Two devices with same
address on SHS CANbus
Check SHS Node Id on device.
AOC
SHS
Invalid State
Combination of valve
states not allowed
Correct Valve conflicts.
AOC
DVM
Vol Flow Low Low
Volumetric Flow lower
than Low Low Limit
Information Only.
AOC
ARV
Vol Flow Low
Volumetric Flow lower
than Low Limit
Information Only.
AOC
ARV
Vol Flow High
Volumetric Flow exceeds
High Limit
Information Only.
AOC
ARV
Vol Flow High High
Volumetric Flow exceeds
High High Limit
Information Only.
AOC
ARV
Pressure Low Low
Pressure lower than Low
Low Limit
Information Only.
AOC
ARV
Pressure Low
Pressure lower than Low
Limit
Information Only.
AOC
ARV
Pressure High
Pressure exceeds High
Limit
Information Only.
AOC
ARV
Pressure High High
Pressure exceeds High
High Limit
Information Only.
AOC
ARV