EasyManua.ls Logo

ABB Relion 670 series - Page 540

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
An analog overexcitation relay would have to evaluate the following integral
expression, which means to look for the instant of time t = t
op
according to
equation
142.
( )( )
opt
2
0
M t Pickup1 0.18dt TD- ³ ×
ò
ANSIEQUATION2300 V1 EN (Equation 142)
A digital, numerical relay will instead look for the lowest j (that is, j = n) where it
becomes true that:
( )
n
2
j k
t M( j) PUV / Hz 0.18 TD
=
D × - ³ ×
å
EQUATION1636 V1 EN (Equation 143)
where:
Dt is the time interval between two successive executions of OEXPVPH (24) and
M(j) -
Pickup1
is the relative excitation at (time j) in excess of the normal (rated) excitation which is given
as Vn/fn.
As long as M > Pickup1 (that is, overexcitation condition), the above sum can only be
larger with time, and if the overexcitation persists, the protected transformer will be
tripped at j = n.
Inverse delays as per figure 273, can be modified (limited) by two special definite
delay settings, namely t_MaxTripDelay and t_MinTripDelay, see figure
272.
Section 8 1MRK505222-UUS C
Voltage protection
534
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals