Installation and User Manual ADPRO FastTrace by Xtralis
68 Doc 11168_12
Base Port Number
Options: <value> Range is 2049 to 65536
Factory Default 15000
The default value = 15000 and should not be changed unless a conflict occurs due to a network
connection of other third-party equipment.
Caution: If the Base Port Number is changed, then all FastTrace units and VideoCentral must
be changed to the same value. Failure to do this on all communicating systems will
result in communications failure.
Connection Timeout
Options: <value> Range is 1 to 300 seconds
Factory Default 5
This setting defines the time that FastTrace will wait for a response from VideoCentral on initial
connection over Ethernet. If this time is exceeded without a response, FastTrace will retry the
connection.
Enable WAN Optimisation
Factory Default: Ye s
Set this checkbox to optimise communications throughput for audio and video transmission. Only
switch this off if advised by Xtralis technical support.
PPP Settings
FastTrace uses PPP when communicating over serial devices, such as modems and terminal
adaptors. Only change these settings if advised by Xtralis technical support.
PPP Request Timeout
Options: <value> Range is 1 to 10 seconds
Factory Default 1
This setting sets the default timeout for negotiating a PPP connection. In some instances, such
as when communicating from GSM to GSM, the time required to negotiate the PPP link can be
significant.
PPP Maximum Retries
Options: <value> Range is 5 to 50
Factory Default 10
This setting sets the default retries for negotiating a PPP connection. In some instances, such as
when communicating from GSM to GSM, the negotiation can fail and the system must retry the
negotiation.
Presidium High Level Interface Properties
Factory Default 15020
If a Presidium is connected to the FastTrace, the Listener Port Number defines on which port the
Presidium High Level Interface communicates with the FastTrace.
This setting must be the same port as that selected in the Presidium Setup Utility, High Level
Interface tab.