EasyManuals Logo

AUTOFLAME Mk8 MM User Manual

AUTOFLAME Mk8 MM
395 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
2 Options & Parameters
Mk8 MM Manual Page | 45
Opt. # Default Range Description
61
3725
MM: Fuel 1 Calorific Value
This is the gross calorific value / higher heating value (HHV) including the
latent heat of vaporisation of water. To set either metric or imperial units,
see parameter 40. If the units are changed, then this option must be
changed accordingly.
100 – 65000
100 = 1.00MJ/m
3
or 100 Btu/ft
3
62
2068
MM: Fuel 2 Calorific Value
This is the gross calorific value / higher heating value (HHV) including the
latent heat of vaporisation of water. To set either metric or imperial units,
see
parameter 40. If the units are changed, then this option must be
changed accordingly.
100 – 65000
100 – 1.00 MJ/kg or 100 BTU/lb
63
2068
MM: Fuel 3 Calorific Value
This is the gross calorific value / higher heating value (HHV) including the
latent heat of vaporisation of water. To set either metric or imperial units,
see parameter 40. If the units are changed, then this option must be
changed accordingly.
100 – 65000
100 – 1.00 MJ/kg or 100 BTU/lb
64
3725
MM: Fuel 4 Calorific Value
This is the gross calorific value / higher heating value (HHV) including the
latent heat of vaporisation of water. To set either metric or imperial units,
see parameter 40. If the units are changed, then this option must be
changed accordingly.
100 – 65000
100 = 1.00MJ/m
3
or 100 Btu/ft
3
65
-
Unused
66
0
MM: Firing Rate Limit
This is the maximum firing rate that can be obtained by the system,
imposed in auto and hand modes. Firing rate limit should not be used with
DTI load index control or sequencing.
0
Disabled
1 – 100
%
67
1
MM: Channel 1 Purge Position
0
Channel 1 to purge position
1
Channel 1 to remain closed for purge
68
0
MM: Channel 2 Purge Position
0
Channel 2 to purge position
1
Channel 2 to remain closed for purge
69
0
MM: Channel 3 Purge Position
0
Channel 3 to purge position
1
Channel 3 to remain closed for purge
70
0
MM: Channel 4 Purge Position
0
Channel 4 to purge position
1
Channel 4 to remain closed for purge
71
0
MM: Continuous Pilot Shut Off Timer
If continuous pilot is enabled (see option/ parameter 111), then after this
timer has elapsed when in continuous pilot firing, the burner will go off.
0
Disabled
1 – 1440
Minutes

Table of Contents

Other manuals for AUTOFLAME Mk8 MM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUTOFLAME Mk8 MM and is the answer not in the manual?

AUTOFLAME Mk8 MM Specifications

General IconGeneral
BrandAUTOFLAME
ModelMk8 MM
CategoryController
LanguageEnglish

Related product manuals