3 Commissioning Procedure
Mk8 MM Manual Page | 99
Figure 3.7.iii Changing a point in single point change
Press to edit the fuel, air and/or VSD commissioned value of that point. Once the changes have
been made, press to save this position. If a point is overwritten, the trim data is cleared and the
trim data will need to be added.
Press to remove the point; there must be a minimum of 3 INTER points.