Technical / Programming Manual
FT128 Rev 2.2
88
programmed to activate 3379. If the smoke is cleared during the delay time, the
sounder base will de-activate otherwise, a general alarm in FT128 will be activated.
23. Same as 22 but for specified zone
24. Same as 22 but for any Zone or Zone-Address in the system..)
25. Output is activated only if the first alarm is an alarm in the specified Zone in the
specified Control Unit. NOTE! This is not valid for manual call points.
26. Output is activated only if the first alarm is an alarm in the specified Zone in the
specified Zone Group.
27. Pre-warning, Output is activated when any of the alarm points in the specified Zone
Group exceeds the pre-warning level. See also 4. Above regarding the quantity.
For information refer to the FT128 Operation Manual.
28. Fire alarm, Output is activated when any of the alarm points in the specified Zone
Group is in alarm. See also 4. Above regarding the quantity. For information refer
to the FT128 Operation Manual.
29. Heavy smoke / heat alarm, Output is activated when any of the alarm points in the
specified Zone Group exceeds the heavy smoke / heat alarm level. See also 4.
Above regarding the quantity. For information refer to the FT128 Operation Manual.
Interlocking
30. Output activated when one or more interlocking inputs, in the specified interlocking
area, are activated.
31. Output activated when the interlocking input, in the specified interlocking
area/point, is activated.
32. Output activated when any interlocking input is activated.
33. Output activated when interlocking inputs, in the specified range, are activated
(from interlocking area no. / point to interlocking area no. / point). See also 4 above
regarding "Quantity".
Disablement
34. Output activated when any Routing equipment output (Fire brigade TX) is
disabled
92
.
35. Output activated when the specified zone is disabled
93
.
36. Output activated when the specified alarm point (zone- address) is disabled
93
.
37. Output activated when any alarm point (zone-address) or zone is disabled
93
.
38. The control expression is true (output activated) when all control outputs of the
types Control, Fire ventilation and Extinguishing are disabled via menu
H2/B4
93
. This output has to be type Control neutral.
39. The control expression is true (output activated) when all control outputs of type
Alarm device are disabled via menu H2/B9
94
. This output must be type Alarm
devices.
40. The control expression is true (output activated) when all control outputs of the
types Control, Fire ventilation and Extinguishing are disabled via menu
H2/B4
93
.
This output has to be type Control neutral.
41. The control expression is true (output activated) when all control outputs of type
Alarm device are disabled via menu H2/B9). This output has to be type Alarm
devices.
92
Which is indicated by LED Fault / Disablements "Fire brigade TX".
93
Which is indicated by LED Fault /Disablements "General Disablements".
94
Which is indicated by LED Fault / Disablements "Alarm devices".