5 RAMO5 motor starter
5.6 LED indicators
128 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
I2 Sensor input SEN I2
Off not connected
not triggered (no input signal)
Green SEN I2 triggered (input signal)
Q1 Actuator output Q1
Only for RAMO5-xx1…!
Off Not actuated
Green ACT Q1 triggered (output signal)
Note:
If the external supply voltage for Q1 (24 V DC) is missing,
no signal is issued at the output.
PWR Off Voltage supply
The 400 V supply voltage is missing or the repair switch is switched off.
Green 400 V supply voltage is present.
Off No fault message
FLT Red Collective fault message
An error has been detected and is permanently present - in the case of:
Motor overload (overcurrent)
Check the motor and the drive unit
(Reset when the motor has cooled)
Short circuit in the motor cable
Check parameters
Thermistor/cable monitoring
Check the motor and the drive unit
(Reset when the motor has cooled)
No motor cable connected (motor outlet socket)
Bridge T1/T2 in the motor terminal box is missing in motors without
temperature sensors
Wire jumper with motor cable disconnected, not closed
( for Service only)
Overload/short circuit on sensor inputs or actuator output
On a temporary or rectified fault this LED flashes until the Reset command
is issued.
Red flashing The detected fault (the fault signal's cause) has been fixed.
The fault signal can now be acknowledged in the OFF/RESET position using
the key switch. The FLT LED goes out.
LED State Description
REV OFF FWD
PWR FLT
SEN I1
I1
ACT Q1
Q1
SEN I2
I2
AS-I
Data
Fault
OFF/RESET