1 Rapid Link 5 system
1.5 Compliance with UL standards
26 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
1.5.3 RASP5
RASP5 speed controllers have been tested in accordance with UL 61800-5
and are approved as "listed".
Table 5: RASP5
Table 6: Short circuit current rating for individual and group protection
Property
Value
Input voltage 480 V AC
Output voltage, maximum 480 V AC
Rated operational voltage for
brake control
180/207 V DC
230/480 V AC
400/480 V AC
Output current 2.5 A (RASP5-2…S1)
4.3 A (RASP5-4…S1)
5.6 A (RASP5-5…S1)
8.5 A (RASP5-8…S1)
Input current
2.4 A (RASP5-2...)
4.1 A (RASP5-4...)
5.3 A (RASP5-5...)
7.8 A (RASP5-8...)
Frequency
50/60 Hz
Phases 3
Output frequency 0 - 320 Hz
Field bus input voltage 30 V DC
Motor protection integrated,
at 105 % of full load
Thermistor monitoring
integrated
Protection class
NEMA 12 / NEMA 12K
Ambient temperature, maximum 40 °C without fan
55 °C with fan
With fuse (UL listed) Circuit-breaker (UL listed)
With built-in
repair switch
Without built-
in local
disconnect
switch
With built-in
repair switch
Without built-
in local
disconnect
switch
Voltage
480 V AC 480 V AC 480 V AC 480 V AC
Short-circuit current, maximum 30 A 30 A 32 A 32 A
Interrupting Rating 10 kA 65 kA 10 kA 10 kA
Devices with an integrated repair switch are approved for use as
motor disconnects (lockout/tagout).