3 Installation
3.6 Motor feeder
110 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
3.6.4 Screened motor cable for RASP5
3.6.4.1 General notes
The following information uses the example of a DESINA MOTORFLEX cable
with 4G1.0 2 x (2 x 0.75) to describe the steps required to establish an EMC-
compliant connection between a mains cable and the RASP.
Figure 68: EMC-compliant connection of the screened motor cable
a 360° contact fuse ≙
Stripping the motor cable ends (radial and longitudinal cut).
Push the screen braid back to reveal the individual conductors.
The conductors B1 (= N) and B2 (= L) for the external brake as well as T1
and T2 for the thermistor have a sheath and a separate screen braid.
These conductors must be stripped separately.
Then slide the outer screen braid of the motor cable back forwards far
enough that a large area of the screen braids of conductors B1/B2 and
T1/T2 are covered and connected with each other.
→
To strip the cable, set the blade so that the conductor insulation
and the screen braid remain undamaged.
→
Cover the screen ends with a rubber grommet or with insulating
tape or textile tape, so that the screen braid does not fray.