8 Parameter list
8.2 Menu structure
166 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
8.2 Menu structure
The acronyms used in the following tables are defined below:
8.3 Parameter groups for RAMO5
8.3.1 Parameter group 0 (Monitor)
Abbreviation Meaning
Default Default setting (the parameter’s value when using the device's
factory settings)
Min./max.
Minimum/maximum value that can be specified
→
None of the parameters in parameter group 0 can be modified
by the user, they are read-only parameters.
Para-
meter
Designation Description Unit
P0-02 Thermistor input1 Thermistor status
0: Motor temperature OK
1: Motor temperature too high
%
P0-03 SEN Status Status of the sensor inputs and ASI pin 4 –
P0-05 T-Controlboard Internal ambient temperature of the device, measured on the control board °C
P0-06 Overload Calculated overload in % above the current set with P1-08.
If the value rises to 100%, the device will trip with error message “iT-Trp”.
%
P0-07 Output frequency Instantaneous output frequency Hz/rpm
P0-09 Motor current Instantaneous output current A
P0-10 Motor Power Rel Motor Power (actual value) in kW/HP kW
P0-13 Trip Log Display of the 4 latest faults –
P0-17 HOA status Key switch status
1: Hand
2: Auto
–
P0-18 FWD/REV status Selector switch status FWD / REV
1: FWD
2: REV
–
P0-19 DO 1 to 3 Status Status of the actuators –
P0-20 DC-Link voltage Instantaneous DC Link Voltage
Display: 600 ≙ 600 V
V
P0-22 TimeToNextService Time remaining to next service
The service interval is set with P2-28.
Hours
P0-24 t-Run PCB in OT Time elapsed, in which the drive has operated with a high temperature at the
PCBs (ambient temperature)
Displays the time in hours and minutes above 80 °C.
The value is used for various internal protective functions.
hh:mm:ss