9 Communication
9.1 A S - In t er fa ce
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 199
9.1.12 Controlling RAMO5 via the AS-Interface
Table 49: Controlling RAMO5
The START signal or enable for the requested operating direction is
issued through DQ0 (FWD) or DQ1 (REV).
DQ2 can be used to switch the actuator output ACT Q1 to High or Low.
Function Signal to RAMO5
AS-Interface outputs AS-Interface inputs
DQ0 DQ1 DQ2 DQ3 DI0 DI1 DI2 DI3
Zero speed 0 0
Anticlockwise rotating field (REV) 0 1
Clockwise rotating field (FWD) 1 0
Zero Speed/reset 1 1
Actuator output = High 1
Actuator output = Low 0
Quick stop ON 0
Quick stop OFF 1
Automatic mode 1
No automatic mode 0
Accumulative error 0
No accumulative error 1
External input SEN I1 via M12 socket
no signal 0
Signal available 1
External input SEN I2 via M12 socket
no signal 0
Signal available 1