8 Parameter list
8.4 Parameter groups for RASP5
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 181
8.4.3 Parameter group 2 (Extended functions)
Table 42: Parameter group 2 (Extended functions)
Parameter Designation Description Unit Min Max DS
P2-01 f-Fix2 Preset Fixed Frequency 2
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm P1-02 P1-01 30 Hz
P2-02 f-Fix3 Preset Fixed Frequency 3
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm P1-02 P1-01 40 Hz
P2-03 f-Fix4 Preset Fixed Frequency 4
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm P1-02 P1-01 50 hz
P2-04 f-Fix5 Preset Fixed Frequency 5
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm P1-02 P1-01 10 hz
P2-05 f-Fix6 Preset Fixed Frequency 6
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm P1-02 P1-01 15 Hz
P2-06 f-Fix7 Preset Fixed Frequency 7
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm P1-02 P1-01 20 hz
P2-07 f-Fix8 Preset Fixed Frequency 8
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm P1-02 P1-01 25 Hz
P2-08 t-SRamp1 Curve shape, temporal S-shape
Linear acceleration and deceleration time according to P1-03
and P1-04.
Timed slurred Transition to Start and End of Acceleration
(P1-03) and Deceleration Ramps (P1-04).
The time set here applies for both ramps.
0.0 = linear
s 0 10 0
P2-09 Overvoltage control The overvoltage control prevents the drive from tripping in
case of regenerative energy feedback from the motor to the
DC link.
When disabled, the drive will trip “Over Voltage” instead of
automatically increasing the motor ramp times.
- 0 1 1
P2-10 REV Enable Activates or deactivates reverse rotation of the motor
0: 0: REV activated - motor is running forward and in reverse
1: REV deactivated - motor will only run forward
- 0 1 0
P2-11 t-acc2 Sets the acceleration ramp time 2 in seconds s 0 3000 5.0
P2-12 n-accMulti1 Frequency / speed, at which the acceleration ramp changes
from t-acc1 to t-acc2.
This can be set to any value between 0 and “f-max” (P1-01)
“Motor Nom Speed” (P1-10) = 0, displayed in Hz.
“Motor Nom Speed” (P1-10) > 0, displayed in rpm.
Frequency / Speed > P2-12 = t-acc2
Frequency / Speed < P2-12 = t-acc1
Hz/rpm 0 P1-01 0
P2-13 t-dec2 Sets the deceleration ramp time 2 in seconds.
Activation via pin 4 at AS-i.
s 0 3000 5.0