8 Parameter list
8.3 Parameter groups for RAMO5
172 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
8.3.4 Parameter group 3 (Mechanical brake and digital inputs)
Table 37: Parameter group 3 (Digital inputs/outputs)
Parameter Designation Description Unit Min Max DS
P3-04 Brake Release Delay Determines the time before the mechanical brake is
released.
s 0 2.50 0
P3-05 Brake Apply Delay Determines the time between the signal to close the brake
and disabling of the drive.
s 0 25.0
0
0
P3-06 SEN I1 Logic 0: normally open
1: normally closed
Note:
Change only after POWER ON / OFF active
0 1 0
P3-07 SEN I2 Logic 0: normally open
1: normally closed
Note:
Change only after POWER ON / OFF active
0 1 0
P3-08 SEN I3 Logic 0: normally open
1: normally closed
Note:
Change only after POWER ON / OFF active
P3-09 SEN I4 Logic 0: normally open
1: normally closed
Note:
Change only after POWER ON / OFF active