9 Communication
9.1 A S - In ter fa ce
198 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
9.1.11 Cable Routing
Do not lay the data bus (AS-Interface) and the sensor and actuator cables
directly parallel with the power bus (mains cable), to a power adapter cable or
to a motor cable. Avoid laying them in a common cable duct or conduit or
tying them together with cable binders. Signal and power cables should, as
far as possible, cross at right angles. This increases their interference immu-
nity (EMC) and therefore operational reliability. Further measures are neces-
sary to ensure EMC-compliant installation of the frequency-controlled
RASP5.
Figure 109: Laying of signal and power cables
a Power cable: Mains connection (power bus, adaptor cable), motor cable
b Control cables: AS-Interface
(data bus), sensor/actuator connection
Route the control cables and signal cables separately from the
mains cables and motor cables.
f 100 mm
(f 3.94“)
ba
a
b
a
b