2 Engineering
2.10 Actuator output
66 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
2.10 Actuator output
Actuator output ACT Q1 (M12 connectors) can be used to trigger external
indicator elements or relays.
In this case, pin 4 of the AS-i connector must be supplied with an external
+24 V DC voltage. The corresponding reference point is pin 2 (0 V) on the
AS-i connector. The actuator (indicator lamp, relay, valve) can be connected
using Q3 pin 4 (+24 V, max. 1 A). The reference point (0 V) is pin 3.
The actuator output is controlled internally; the response time is up to 20 ms.
The permitted length of the connection cable is 20 m.
Maximum load current
The maximum permissible load current is 1 A with external power
supply.
If no external power supply is present, the maximum permissible load
current is only 100 mA.
The actuator output is short-circuit proof.
In the event of an overload or short-circuit, a group fault signal will be genera-
ted and the FLT LED will light up red to indicate this.
Actuator output
An actuator output is only present in the version RAMO5xx1…-
…S1.
RA-XAZ2-1M
AS-I
Data
Fault
I1
SEN I1
ACT Q1
Q1
SEN I2
I2
PWR FLT
1–
2–
3 0 V actuator output (ACT Q1)
4 24 V DC actuator output (ACT Q1)
5
1
3
2
4
5
24 V DC
1 (AS-Interface+)
2 External 0 V
3 (AS-Interface–)
4 External 24 V
2
4
1
3