1 Rapid Link 5 system
1.5 Compliance with UL standards
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 25
1.5.2 RAMO5
The RAMO5 motor starters have been tested in accordance with UL 60947-
4-2 and are approved as “listed”.
Table 3: RAMO5
Table 4: Short circuit current rating for individual and group protection
RAMO5 motor starters can be installed and operated under the following
conditions: The device is suitable for use on a circuit capable of delivering not
more than 65000 A rms symmetrical amperes, 480 V:
• When protected by 30-A fuses or
• when protected by a circuit breaker having an interrupting rating not less
than 65000 A rms symmetrical amperes, 480 V, 32 A maximum.
Only for use with flexible cable connected drives is at the discretion of the
AHJ.
Installation may be limited to NFPA 79 applications.
Property Value
Input voltage 480 V AC
Output voltage 480 V AC
Rated operational voltage for brake control 180/207 V DC
230/480 V AC
400/480 V AC
Input current 6.6 A
Output current 6.6 A
Phases 3
Frequency
50/60 Hz
Control voltage, external
24 V DC
Field bus input voltage 30 V DC
Motor protection integrated
Thermistor monitoring integrated
SCCR → Table 4
Protection class IP65 / NEMA 12
Ambient temperature, maximum 55
°
C
With fuse (UL listed) Circuit-breaker (UL listed)
With built-in
repair switch
Without built-
in local
disconnect
switch
With built-in
repair switch
Without built-
in local
disconnect
switch
Voltage
480 V AC 480 V AC 480 V AC 480 V AC
Short-circuit current, maximum
30 A 30 A 32 A 32 A
Interrupting Rating
10 kA 65 kA 10 kA 10 kA
→
Devices with an integrated repair switch are approved for use as
motor disconnects (lockout/tagout).