5 RAMO5 motor starter
5.7 Configure specialist settings
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 131
5.7.3 Sensor inputs
Sensor inputs I1 and I2 are designed for rising-edge input signals (N/O clo-
sing contact, fail-safe).
In the default setting, parameters P3-06 and P3-07 are set to 0.
When using sensors (open) that switch to zero, parameters P3-06 and P3-07
must be set to 1. The signal is then inverted.
Figure 81: Configuring sensors inputs SEN I1 and SEN I2
SEN I1, SEN I2
→
1
SEN I1, SEN I2
→
0
Parameter Designation Description Unit Min Max DS
P3-06 SEN I1 logic 0: N/O closing contact
1: N/C opening contact
Note:
A change only becomes active after
POWER ON/OFF.
– 0 1 0
P3-07 SEN I2 logic 0: N/O closing contact
1: N/C opening contact
Note:
A change only becomes active after
POWER ON/OFF.
– 0 1 0