1 Rapid Link 5 system
1.6 Selection criteria
28 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
1.6 Selection criteria
Select a RAMO5 or RASP5 device according to the supply voltage U
LN
of
the supply system and the rated current of the assigned motor .
The circuit type ( / ) of the motor must be selected for the supply voltage
.
The RASP5 unit’s rated output current I
e
must be greater than or equal to the
rated motor current. For RAMO5, current monitoring must be set to the
rated motor current.
Figure 7: Selection criteria
When selecting the drive, the following criteria must be known:
• Type of motor (three-phase asynchronous motor)
• Mains voltage = rated operating voltage of the motor (e.g. 3 AC ~ 400 V),
• Rated motor current (recommended value, dependent on the circuit type
and the supply power supply)
• Load Torque,
• Starting torque,
• Ambient temperature.
ATTENTION
Do not disconnect or connect power connectors (mains, motor)
while RAMO5 and RASP5 are operational.
230 / 400 V ∆ /
4.6 / 2.6
1.1
0.81
ϕ
cos
kW
min
-1
1430 50 Hz
A
②
①
U, I, f
③