5 RAMO5 motor starter
5.6 LED indicators
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 127
5.6 LED indicators
The LEDs indicators of the RAMO5 motor control unit display the operating
states and allow problems to be quickly diagnosed.
LED State Description
FWD Clockwise rotating field of motor voltage (U–V–W)
Off Not actuated
Green enabled (RUN-Mode)
Flashing
(green)
controlled:
but inhibited by the Quick stop function of sensor inputs I1 and I2
But blocked because when the supply voltage was switched on
(400 V or ASi), the key switch was in the MANUAL position.
A Reset command required.
REV Counterclockwise rotating field of motor voltage (W–V–U)
Only for reversing starter RAMO5-W…!
Off Not actuated
Green enabled (RUN-Mode)
Green flashing controlled:
but inhibited by the Quick stop function of sensor inputs I1 and I2
But blocked because when the supply voltage was switched on
(400 V or ASi), the key switch was in the MANUAL position.
A Reset command required.
AS-I AS-Interface
Data
Off ASi electronics have no supply voltage:
Check ASi connection cables
Check ASi power supply unit (head-end controller)
Green Communication active, normal operation
Red No communication:
Head-end controller (master) in STOP mode.
RAMO5 not entered or entered with the wrong address (ID).
RAMO5 in Reset mode.
Yellow flas-
hing, red
ASi address = 0
Adjust ASi address
Green,
Red flashing
fatal peripheral error, internal ASi error
Fault
Red No data exchange, communication error
Red flashing Peripheral fault,
I1 Sensor input SEN I1
Off not connected
not triggered (no input signal)
Green SEN I1 triggered (input signal)
REV OFF FWD
PWR FLT
SEN I1
I1
ACT Q1
Q1
SEN I2
I2
AS-I
Data
Fault
OFF/RESET