8 Parameter list
8.4 Parameter groups for RASP5
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 187
8.4.6 Parameter group 5 (Communication)
Table 45: Parameter group 5 (Communication)
Parameter Designation Description Unit Min Max DS
P5-01 RS485-0 Address Unique address of the drive (keypad, OP bus) 1 63 1
P5-02 COM Loss Timeout With an active communication link, if a valid telegram is not
received by the drive within the period set with this para-
meter, the drive will react as set in P5-03.
s 0 5.0 2
P5-03 Action@Communica-
tion Loss
Device reaction after “Communication Loss” occurs.
Possibilities device dependent
0: Trip
1: Ramp to stop, then trip
2: Ramp to stop only (no trip)
3: Run at preset speed 2 (P2-01)
0 3 0
P5-04 FieldbusRampControl Fieldbus Ramp Control
0: OFF. Ramps are controlled by internal drives parameters
1: ON. Ramps are controlled by the fieldbus.
0 1 0
P5-05 NETSendPZD3 Configuration of the 3rd process data word PDO-3 from the
drive to the network master during cyclic communication.
0: Motor current in A with one decimal place,
e.g. 100 10.0 A
1: Output power in kW with two decimal places,
e.g. 400 4.00 kW
2: Status of the sensor inputs (SEN I).
Bit 0 = status SEN II1, bit 1 = status SEN I2, etc.
3: Internal temperature. -500 - 1500 -50 - 150 °C
0 6 0
P5-06 NETSendPZD4 Configuration of the 4th process data word PDO-3 from the
drive to the network master during cyclic communication.
0: Motor current in A with one decimal place,
e.g. 100 10.0 A
1: Output power in kW with two decimal places,
e.g. 400 4.00 kW
2: Status of the sensor inputs (SEN I).
Bit 0 = status SEN II1, bit 1 = status SEN I2, etc.
3: Internal temperature. -500 - 1500 -50 - 150 °C
0 6 1
P5-07 NETReceivePZD3 Configuration of the 3rd process data word PDI-3 from the
network master to the drive during cyclic communication.
0: reserved
1: User defined ramp times, e.g. 500 5.00 s.
0 3 1
P5-08 NETReceivePZD4 Configuration of the 4th process data word PDI-4 from the
network master to the drive during cyclic communication.
0: reserved
0 3 0