EasyManua.ls Logo

Eaton Rapid Link 5 - LED Indicators

Eaton Rapid Link 5
249 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 RASP5 speed controller
6.6 LED indicators
144 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
6.6 LED indicators
The LED indicators of the RASP5 speed controller display the operating sta-
tes and allow problems to be quickly diagnosed.
LED Display Description
FWD Clockwise rotating field of motor voltage (U–V–W)
Off Not actuated
Green enabled (RUN-Mode)
Flashing
(green)
controlled:
But inhibited by the Quick stop function of the sensor inputs
But blocked because when the supply voltage was switched on
(400 V or ASi), the key switch was in the MANUAL position.
A Reset command required.
STO signal present (inhibit)
REV Counterclockwise rotating field of motor voltage (W–V–U)
Off Not actuated
Green enabled (RUN-Mode)
Flashing
(green)
controlled:
But inhibited by the Quick stop function of the sensor inputs
But blocked because when the supply voltage was switched on
(400 V or ASi), the key switch was in the MANUAL position.
Reset command required.
STO signal present (inhibit)
AS-I AS-Interface
Data
Off ASi electronics have no supply voltage:
Check ASi connection cables
Check ASi power supply unit (master control)
Green Communication active, normal operation
Red No communication:
Head-end controller (master) in STOP mode.
RASP5 not entered or entered with the wrong address (ID).
RASP5 in Reset mode.
Yellow flas-
hing, red
ASi address = 0
Adjust ASi address
Green,
Red flashing
fatal peripheral error; internal ASi error
Fault
Red No data exchange, communication error
Red flashing Peripheral fault,
I1 Sensor input I1
Off not connected
Not triggered (no input signal)
Green SEN I1 triggered (input signal)
REV OFF FWD
PWR FLT
AS-I
Data
Fault
OFF/RESET
SEN I1/I3
I1
SEN I2/I4
I2
I3
I4
STO
FAN

Table of Contents

Related product manuals