3 Installation
3.2 Instruction leaflets
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 83
3.2.2 Clearances
Figure 39: Clearances for thermal air cooling (example: RASP5)
Depending on the version, thermal clearances must be provided around the
RAMO5 and RASP5 Rapid Link 5 modules. Unobstructed handling must also be
ensured for versions with a repair and maintenance switch (
RAMO5-…-...RS1
and RASP5-…-...R…S1
) and in the area of the plug-in power connections .
The table below lists the recommended minimum clearances.
Position Instance RAMO5
Clearance
RASP5
Clearance
mm mm
top
without repair and maintenance switch 25 100
with repair and maintenance switch ~150 ~150
bottom
without power connection 25 100
with power connection ~100 ~100
front
without fan 15 25
•with fan
50
lateral
without repair and maintenance switch ~0
1)
~0
1)
with repair and maintenance switch ~150 ~150
without power connection ~0
1)
~0
1)
with power connection ~100 ~100
1) At an installation altitude up to 1000 m and at an ambient temperature of up to +40 °C no clearance is required
to the sides.
Units installed in higher ambient temperatures (up to a maximum of +50 °C), pulse frequencies f
PWM
(up to
maximum 32 kHz) and higher set-up altitudes (up to 2000 m) require lateral spacing of at least 20 mm.
Devices with high magnetic fields (e.g. reactors or transformers)
must not be mounted close to RAMO5 or RASP5 units.