5 RAMO5 motor starter
5.7 Configure specialist settings
134 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
5.7.6 Monitoring the low current limit
When set to P6-05 = 1 (= ON), an error message will be issued (FLT LED will
light up red) if a phase (L1, L2, L3) carries less than 25 % of the rated current
l
e
.
5.7.7 Quick stop
The Quick stop function is activated using parameter P5-10 and deactivated
with DQ3. The Quick stop function is enabled via DQ3 (ASi).
Parameter Designation Description Unit Min Max DS
P6-05 Action@Under-
load Motor
Device response (depending on device)
after “Motor underload” occurs.
0: deactivated
1: Error (shutdown)
– 0 1 0
Parameter Designation Description Unit Min Max DS
P5-10 Disable
quick stop
0: Quick stop via sensors deactivated.
1: Quick stop via sensors activated
(ASi signal active).
– 0 1 0
P5-10 DQ3 Function Description
1 0 Quick stop ON Response to sensors
1 1 Quick stop OFF No response to sensors
0 0 None DQ3 signals will not be transmitted
0 1 None DQ3 signals will not be transmitted