6 RASP5 speed controller
6.7 Configuration of specific settings
148 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
6.7.3 Sensor inputs
The four sensor inputs SEN I1, SEN I2, SEN I3 and SEN I4 are designed for
rising-edge input signals (N/O closing contact, fail-safe).
In the factory setting, parameters P3-06, P3-07, P3-08 and P3-09 are set to 0.
When using sensors that switch to zero (normally closed), the parameters
must be set to the value 1. The signal is then inverted.
Figure 90: Configure the sensor inputs SEN I1, SEN I2, SEN I3, SEN I4
SEN I1, SEN I2,
SEN I3, SEN I4
1
SEN I1, SEN I2,
SEN I3, SEN I4
0
Parameter Designation Description Unit Min Max DS
P3-06 SEN I1 logic 0: N/O closing contact
1: N/C opening contact
Note:
A change only becomes active after
POWER ON/OFF.
0 1 0
P3-07 SEN I2 logic 0: N/O closing contact
1: N/C opening contact
Note:
A change only becomes active after
POWER ON/OFF.
0 1 0
P3-08 SEN I3 logic 0: N/O closing contact
1: N/C opening contact
Note:
A change only becomes active after
POWER ON/OFF.
0 1 0
P3-09 SENI4 logic 0: N/O closing contact
1: N/C opening contact
Note:
A change only becomes active after
POWER ON/OFF.
0 1 0
Sensors SEN I3 and SEN I4 require a Y connector of the type
RA-XM12-Y.