10 Error Messages
10.2 Error Messages
236 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
10.2 Error Messages
The following table lists the error messages (fault codes) and possible cau-
ses and indicates corrective measures.
10.2.1 RAMO5 error messages
Table 57: List of error messages for RAMO5
Message
Error no.
[dec]
Possible cause and remedy
Stop Ready for operation. There is no drive enable signal present.
There are no error messages present.
no-F
(t 00 Shown for P0-13 if there are no messages in the error register.
I.t-trP 04 Motor overload. The thermal protection mechanism has tripped as a result of
the device being run above the motor nom current set with P1-08 longer than
a specific time.
Check to make sure that the motor data was entered correctly in P1-08.
Check the motor’s connection configuration (e.g., start/delta)
Make sure that the motor is not being mechanically blocked and that there
are no additional loads on the motor.
O.Volt
06 Overvoltage in DC-Link
The DC-Link Voltage value can be viewed using parameter P0-20.
P0-36 contains a fault register with the last values before the unit was
switched off (sample time: 256 ms).
Check to make sure that the supply voltage falls within the range for which
the variable frequency drive is sized.
V.Volt
07 Undervoltage in DC-link
Note:
Generally, this message will appear when the supply voltage is switched off
on the device and the DC-Link voltage dies away.
In this case, there is no fault.
If the message appears during operation:
Check whether the power supply voltage is too low.
Check all components/devices in the feeder circuit (circuit-breaker,
contactor, choke, etc.) to make sure they are connected properly and have
an adequate contact resistance.
P-dEf
10 The parameters’ default settings have been loaded.
Press the STOP button: The drive can then be reconfigured.
SC-ObS
12 Communication fault with an external operating unit or with a PC.
Check connections.
P-LOss
14 Failure of one phase of the infeed
dAtA-F 17 Error in internal memory. The parameters have not been saved and the default
settings have been loaded.
Change the parameter values (again) and save them once more.
If the message appears again, please contact your nearest Eaton sales
branch.
dAtA-E 19 Error in internal memory. The parameters have not been saved and the default
settings have been loaded.
Change the parameter values (again) and save them once more.
If the message appears again, please contact your nearest Eaton sales
branch.
F-Ptc
21 Motor PTC thermistor overtemperature