5.7 Configure specialist settings
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 133
Parameter P1-13
Table 24: Signal detection for RAMO5-D… direct starter
Table 25: Signal detection for RAMO5-W… reversing starter
5.7.5 Phase change
Parameter P6-08 changes the rotating field at the output of RAMO5-W…
from FWD to REV. The control logic and the LED indicators remain in the
FWD function.
Manual mode Auto mode
P1-13 SI1 SI2 SI1 SI2
0
1 No function No function No function No function
2 Stop for edge control Stop for edge control Stop for edge control Stop for edge control
3 No function No function Stop for edge control No function
4 Stop for edge or signal control No function Stop for edge control No function
Manual mode Auto mode
P1-13 SI1 SI2 SI1 SI2
0
1 No function No function No function No function
2 No function No function Stop for edge control No function
3 No function No function Stop in FWD mode with edge
control
Stop in REV mode with edge
control
4
Stop in FWD mode for edge or
signal control
Stop in REV mode for edge or
signal control
Stop in FWD mode for edge or
signal control
Stop in REV mode for edge or
signal control
For RAMO5-W… the P6-08 parameter setting should be chan-
ged by competent users according to the instructions in the
manual.
For RAMO5-D…, parameter P6-08 has no function.
Parameter Designation Description Unit Min Max DS
P6-08 Change Phases
equence Motor
Changes the sequence of the output
phases.
This prevents two phases of the motor
cable from having to be swapped in
case the motor runs in the wrong direc-
tion.
0: U – V – W (clockwise rotating field)
1: U – W – V (counterclockwise rota-
ting field)
0 1 0