7 Parameterization
7.2 Parameterization using OLED operating unit
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 163
7.2.3 Reset parameters (RESET)
Table 32: Resetting parameters (RESET)
7.2.4 Extended parameter set
Table 33: Open and exit the extended parameter set
Commands Description
Reset to default settings
++
Press the and and STOP buttons together or simultaneously and hold them down
for two seconds.
-> All parameters will be reset to their default settings.
The display will show
P-dEF.
Reset after a fault
Press the STOP button to reset a fault message.
The display will show
StoP.
Commands Description
Open the extended parameter set
Press the OK button and hold it down for two seconds in order to
access the parameter interface.
-> The display shows the parameter that was used last.
Use the and buttons to select parameter P1-14.
Press the OK button.
Use the or buttons to select the password set using parameter
P2-32 (Level 2, default setting 101).
Press the OK button to confirm.
->
The extended parameter set is now available.
Exit the extended parameter set
Use the and buttons to set a value for P1-14 that does not match
the password (P2-32).
Press the OK button to confirm.
->
Only the basic parameters, i.e. the parameters in the first parameter
group (P1-01 to P1-14), will now be accessible.