8 Parameter list
8.4 Parameter groups for RASP5
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 175
8.4 Parameter groups for RASP5
8.4.1 Parameter group 0 (Monitor)
Table 40: Parameter group 0 (Monitor)
Parameter Designation Description Unit
P0-02 Thermistor input1 Thermistor status
0: Motor temperature OK
1: Motor temperature too high
P0-03 SEN Status Status of the sensor inputs and ASI pin 4
P0-04 f-PreRamp Speed reference in front of the ramp Hz/rpm
P0-05 T-Controlboard Internal ambient temperature of the device, measured on the control board °C
P0-06 Overload Calculated overload in % above the current level set with P1-08. If the value
rises to 100 %, the device will trip with error message “iT-Trp”.
%
P0-07 Output frequency Instantaneous output frequency Hz/rpm
P0-08 Motor speed Motor speed (calculated or measured) Hz/rpm
P0-09 Motor current Instantaneous output current A
P0-10 Motor Power Rel Motor Power (actual value) in kW/HP kW
P0-11 Motor voltage Instantaneous output voltage V
P0-12 Motor torque Motor torque
Display: 1000 100%
%
P0-13 Trip Log Display of the 4 latest faults
P0-14 Magnetizing current I
d
Calculated magnetizing current I
d
– providing an autotune has been completed successfully.
A
P0-15 Torque current I
q
Calculated torque-producing current I
q
– providing an autotune has been completed successfully.
A
P0-16 DC-Link Voltage Ripple DC-Link Voltage Ripple V
P0-17 HOA status Key switch status
1: Hand
2: Auto
P0-18 FWD/REV status Selector switch status FWD / REV
1: FWD
2: REV
P0-19 DO 1 to 3 Status Status of the actuators
P0-20 DC-Link voltage Instantaneous DC Link Voltage
Display: 600 600 V
V
P0-21 Heatsink temperature Instantaneous Heatsink Temperature
Display: 40 40 °C
°C
P0-22 TimeToNextService Time remaining to next service (in hours).
The service interval is set with P2-28.
Hours
P0-23 t-Run IGBT in OT Time elapsed, in which the drive has operated with a high heatsink
temperature
Displays the time in hours and minutes above 85 °C.
The value is used for various internal protective functions.
hh:mm:ss