8 Parameter list
8.4 Parameter groups for RASP5
176 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
P0-24 t-Run PCB in OT Time elapsed, in which the drive has operated with a high temperature
at the PCBs (ambient temperature)
Displays the time in hours and minutes above 80 °C.
The value is used for various internal protective functions.
hh:mm:ss
P0-25 f-PostRamp Speed reference after the ramp Hz/rpm
P0-26 kWh Meter Energy consumption kWh Meter (not resettable)
Displays the energy consumption in kWh. When the value reaches 1000,
it is reset to 0 and the number of MWh in P0-27 is increased by 1.
The value cannot be reset and shows together with P0-27 the energy
consumption since the day of manufacture.
kWh
P0-27 MWh Meter Energy consumption MWh Meter (not resettable)
Displays the energy consumption in kWh. The value cannot be reset and
shows together with P0-26 the energy consumption since the day of manu-
facture.
MWh
P0-28 Application Version Application Version
Level 1: Application version + checksum
Level 2: System version + checksum
P0-28 System Version System version
P0-29 n/a Device information
NoOfInputPhases Number of input phases
FrameSize Frame size
kW/HP Motor output
Power@Ue Device Power at Device Voltage Rating
Device voltage Device Voltage Rating
DeviceType Device type
P0-30 Serial number Serial Number of the device
P0-31 t-Run Total operating time of the drive since the date of manufacture
Displayed in hours, minutes and seconds.
Pressing Δ on the drive keypad will change the display from “hours” to
“minutes and seconds”.
hh:mm:ss
P0-32 t-Run since Restart Run time since power on or last Reset
Total operating time of the drive since the last trip occurred or power down
in hours, minutes and seconds.
Pressing Δ on the drive keypad will change the display from “hours” to
“minutes and seconds”.
hh:mm:ss
P0-33 t-Run since Trip Total operating time of the drive since the last trip occurred
Displayed in hours, minutes and seconds.
Pressing Δ on the drive keypad will change the display from “hours” to
“minutes and seconds”.
hh:mm:ss
P0-34 t-HoursRun Enable Total operating time of the drive since the last drive ENABLE signal was
applied
Displayed in hours, minutes and seconds.
Pressing Δ on the drive keypad will change the display from “hours” to
“minutes and seconds”.
hh:mm:ss
P0-35 Fan Runtime Run time of the integrated fan (not resettable)
Displayed in hours. (F is displayed at the beginning of the line).
hh:mm:ss
P0-36 DC-Link Log DC-Link voltage log
Displays the most recent 8 samples of the DC bus voltage prior to a drive
trip condition occurring. The sample interval is 256 ms.
V
Parameter Designation Description Unit