8 Parameter list
8.4 Parameter groups for RASP5
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 177
P0-37 DC-Link V-ripple log DC-Link Voltage Ripple Log
Displays the most recent 8 samples of the ripple of the DC bus voltage prior
to a drive trip condition occurring. The sample interval is 20 ms.
V
P0-38 Heatsink log Heatsink temperature log
Displays the most recent 8 samples of the heat sink temperature prior to a
drive trip condition occurring. The sample interval is 30 s.
°C
P0-39 AmbientTemp Log Internal Ambient Temperature Log
Displays the most recent 8 samples of the internal ambient temperature
prior to a drive trip condition occurring. The sample interval is 30 s.
°C
P0-40 MotorCurrent Log Motor current log
Displays the most recent 8 samples of the Motor current prior to a drive trip
condition occurring. The sample interval is 256 ms.
A
P0-41 FaultCounter Overcurrent Counts how often “Overcurrent” occurred
P0-42 FaultCounter DC-Overvoltage Counts how often “DC-Overvoltage” occurred
P0-43 FaultCounter DC-Undervoltage Counts how often “DC-Undervoltage” occurred
P0-44 FaultCounter Overtemperature Heatsink Counts how often “Overtemperature Heatsink” occurred
P0-45 FaultCounter Overcurrent Brake Chopper Counts how often “Overcurrent Brake Chopper” occurred
P0-46 FaultCounter Overtemperature Ambient Counts how often “Overtemperature Ambient” occurred
P0-47 FaultCounter Internal Fault (IO) Counts how often “Internal Fault (IO)” occurred
P0-48 FaultCounter Internal Fault (DSP) Counts how often “Internal Fault (DSP)" occurred
P0-49 FaultCounter Local COM Loss Counts how often “Local COM Loss” occurred
P0-50 FaultCounter Communication Loss Counts how often “Communication Loss” occurred
P0-51 Input Data Value Input Data Value
Process Input Data (PDI, received from the fieldbus).
There are four entries for this parameter (PDI1, …, PDI4).
P0-52 Output Data Value Output Data Value
Process Output Data (PDO, received from the fieldbus).
There are four entries for this parameter (PDO1, …, PDO4).
P0-53 Phase U Current Offset Ref. Phase U, current offset and reference
(value for diagnosis in case of problems)
P0-54 Phase V Current Offset Ref. Phase V, current offset and reference
(value for diagnosis in case of problems)
P0-55 Phase W Current Offset Ref. Phase W, current offset and reference
(value for diagnosis in case of problems)
P0-56 t-PowerOn Total time for which the drive was powered up since the day of
manufacture.
Displayed in hours, minutes and seconds.
Pressing Δ on the drive keypad will change the display from “hours” to
“minutes and seconds”.
hh:mm:ss
P0-57 V d axis V
d
and V
q
of the stator voltage
1. value = V
d
(d at the beginning of the line)
Pressing the Δ on the drive keypad will change the display to V
q
(q at the
beginning of the line).
V
V q axis
P0-58 UserProgramID ID of a program generated by the Function Block Editor.
This ID can be set by the user when developing the program.
P0-59 Value@Pointer Pointer on an internal parameter
Displays the value selected with P5-09.
P0-60 Reserved
Parameter Designation Description Unit