3 Installation
3.4 Power bus
94 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
3.4.2 Round cable
3.4.2.1 Round cable junction RA-C2-S1-4
The RA-C2-S1-4 round cable junction is a T connector for the RA-C3/C2-
1.5HF plug-in power adapter cable. It makes it possible to connect a
Rapid Link 5 module (RAMO5/RASP5) directly.
Figure 54: Round cable junction RA-C2-S1-4
Insulation piercing terminals are used for conductor contacting in the
power bus.
The bushings are dimensioned for a conductor with an outer diameter from
10 to 16 mm.
Accessories (seal inserts, locking clip, the fully wired bushing insert, etc.)
are included as standard.
For mounting, secure the round pipe outlet on the ground using the
appropriate screws (M5).
Strip the round cables to a length of 130 mm (two radial cuts, one longi-
tudinal cut) using, for example, a Weidmüller AM16 stripping tool.
Cut the seals radially, place them around the cable jacket
and insert
the
seals into the U-shaped contour provided in the cable outlet.
To strip the cable, position the blade in such a way that the
conductor insulation will not be damaged.
Two pairs of seals for cable outer diameters from 10 to 13 mm
and from 13 to 16 mm are always included as standard.
Only these matched seal inserts installed correctly guarantee
protection class IP65.
The round cable must be laid without tension.
Install only one conductor per terminal.