6 RASP5 speed controller
6.4 Specific technical data
138 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
6.4 Specific technical data
The following tables show the technical data of the RASP5 speed controller
in the individual power classes with the assigned motor power.
The motor power allocation is based on the rated operational
current.
The motor power indicates the respective active power output
to the drive shaft of a normal, four pole, internally or externally
ventilated three-phase asynchronous motor with 1500 rpm
(at 50 Hz) and 1800 rpm (at 60 Hz).
Symbol Unit RASP5-2… RASP5-4… RASP5-5… RASP5-8…
Rated current (I
e
)I
e
A 2.4 4.3 5.6 8.5
Overload current for 60 s every
600 s at 40 °C
I
L
A 3.6 6.5 8.4 12.75
Startup current for 2 s
every 20 s at 40 °C
I
L
A 4.8 8.6 11.2 17
Apparent power at 400 V rated
operation
SkVA
1.84 3.27 4.24 6.49
Assigned motor power at 440 V,
60 Hz
PkW0.75 1.5 2.2 4
PHP1 2 3 5
Setting range
current limitation (P1-08)
l
2
A 0.2 - 2.4 0.4 - 4.3 0.5 - 5.6 0.8 - 8.5
Power supply side (primary side)
Number of phases 3 3 3 3
Rated voltage U
LN
V 380 V - 15 % - 480 V + 10 %, 50/60 Hz
(380 - 480 V ±0 %, 45 - 66 Hz ±0 %)
Input current I
LN
A 2.5 4.1 5.3 7.8
Braking
Braking value I/I
e
% 30 30 30 30
Switch-on threshold for the
braking transistor
U
DC
VDC 765 765 765 765