8 Parameter list
8.3 Parameter groups for RAMO5
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 169
8.3.2 Parameter group 1 (Basic)
Table 35: Parameter group 1 (Basic)
Parameter Designation Description Unit Min Max DS
P1-08 Motor Nom Current Motor rated Current
By setting the “Motor Nom Current” in the drive, the
motor overload protection is configured to match the
motor rating.
When the measured motor current exceeds “Motor
Nom Current”, the decimal points on the display will
flash to indicate an overload condition.
If this condition persists, the drive will eventually trip,
displaying I.t-trP, preventing thermal overload of
the motor.
Amps 0.3 6.6 6.6
P1-13 SEN Config Select Configuration of sensor inputs with a fix set of combi-
nations
– 1 4 1
P1-14 Access key Entry of the password to get access to the extended
parameter set.
The value to be put in is determined by the level to be
accessed.
Level 2 (access to parameter groups 0 to 8):
P1-14 = P2-32 (factory setting: 101)
– 0 65535 0