5 RAMO5 motor starter
5.7 Configure specialist settings
130 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
5.7.2 Set the rated motor current (P1-08)
Before commissioning the RAMO5 motor starter, the current monitor must
be set to the rated motor current (using parameter P1-08).
Figure 80: Set rated motor current
Table 23: Parameter P1-08
ATTENTION
Parameter P1-08 can only be changed if the key switch is in the
OFF/RESET position.
Switching the key switch during operation may cause the motor
to start up accidentally.
Parameter Description Unit Value range
P1-08 Nominal motor current A 0.3 - 6.6
1410 min
230/400 V 3.2/1.9 A
50 Hz
-1
1,1KW
cos ϕ 0.79
P1-08