10 Error Messages
10.2 Error Messages
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 237
O-hEAt 23 The measured ambient temperature exceeds the specified value.
Check the device's internal fan.
Make sure that there is enough free space around the device.
If possible: Reduce load.
V-torq
25 Underload
If the motor current is 25 % below the rated motor current, this error message
appears.
OVt-Ph
49 A phase in the motor cable is not connected or is disconnected.
Sc-FO1
50 No valid field bus telegram was received within the time specified in P5-02.
Check to make sure that the network master is working correctly.
Check connecting cables.
Increase the value of P5-02 to an acceptable value.
OF-01
60 No internal connection to an optional card
OF-02 61 Optional module in undefined operating state
OF-10 70 Sensor fault - overload or short circuit
Message Error no.
[dec]
Possible cause and remedy