P5-09 PointerToParameter Pointer to an internal variable
P5-09 defines the internal variable (or the parameter), whose
value is displayed with P0-59. In addition the value can be
transferred to a fieldbus master vir Process Data Word 3
(PZD3, to be set with P5-05) or 4 (PZD4, to be set with P5-06).
P5-09 is mostly used in conjunction with the Function Block
Editor.
– 0 200 0
P5-10 Disable QuickStop 0: Quick stop via sensors deactivated
1: Quick stop activated via sensors; DQ3 signal active
– 0 1 0
P5-11 AS-i command confi-
guration
Configuration of the 4 AS-Interface outputs DQ0, …, DQ3
0: Clockwise rotation, anticlockwise rotation, FF1 - FF4
(binary coded via Select f-Fix Bit0-1); FWD + REV = Reset
1: Clockwise rotation, FF1 - FF8 (binary coded via Select f-Fix
Bit0-2)
2: Clockwise rotation, selection between 1st and 2nd ramp
time (0= P1-03, P1-04 / 1 = P2-11, P2-13), FF1 - FF4 (binary
coded via Select f-Fix Bit0-1)
– 0 2 0