10 Error Messages
10.2 Error Messages
240 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
P-LOss 14 Failure of one phase of the infeed
h O-I 15 Overcurrent at output
See Error no. 03.
th-f
(t 16 Malfunctioning heat sink thermistor.
Please contact your nearest Eaton sales branch.
dAtA-F
17 Error in internal memory. The parameters have not been saved and the default
settings have been loaded.
Change the parameter values (again) and save them once more.
If the message appears again, please contact your nearest Eaton sales
branch.
dAtA-E
19 Error in internal memory. The parameters have not been saved and the default
settings have been loaded.
Change the parameter values (again) and save them once more.
If the message appears again, please contact your nearest Eaton sales
branch.
F-Ptc
21 Motor PTC thermistor overtemperature
O-hEAt 23 The measured ambient temperature exceeds the specified value.
Make sure that the required clearance around the device is being main-
tained and that cooling air can flow through the vents on the device
unimpeded.
Reduce the switching frequency with P2-22.
If possible: Reduce load.
OVt-F
26 Device output fault
Please contact your nearest Eaton sales branch.
Sto-F
29 Internal STO circuit fault
Please contact your nearest Eaton sales branch.
V-torqM
30 Underload in the motor range
V-torqW 32 Underload in the field weakening range
AtF-01 40 Motor identification failed:
The measured stator resistance varies between the phases.
Make sure that the motor is connected properly and working correctly.
Check the motor windings to make sure they have the same resistance
values.
AtF-02
41 Motor identification failed:
The measured stator resistance is too large.
Make sure that the motor is connected properly and working correctly.
Check to make sure that the device’s rated output matches the motor’s
rated output. The difference should not exceed one full output class.
AtF-03
42 Motor identification failed:
The measured motor inductance is too low.
Make sure that the motor is connected properly and working correctly.
AtF-04 43 Motor identification failed:
The measured motor inductance is too high.
Make sure that the motor is connected properly and working correctly.
Check to make sure that the device’s rated output matches the motor’s
rated output. The difference should not exceed one full output class.
AtF-05
44 Motor identification failed:
The measured motor parameters do not match.
Make sure that the motor is connected properly and working correctly.
Check to make sure that the device’s rated output matches the motor’s
rated output. The difference should not exceed one full output class.
Message
Error no.
[dec]
Possible cause and remedy