GAMATRONIC ELECTRONIC INDUSTRIES LTD.
84
POWER
+
PARALLEL
UPS,
USER GUIDE
,
REL
.
2.0
Note: The Alarm Integration Factor determines the number of times that the controller polls and retries to
determine the USP status before deciding on an error status. Setting the alarm integration factor too
low will cause spurious alarms to be generated; conversely, setting the alarm integration factor too
high may result in an alarm only being raised when it is already too late to take corrective action.