2. Select Alarm set:
[Main Menu > SETUP > (password) > Ent]
1> Alarm Set 5> Time 9> Silicon
2> Module Conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service 1
Figure 118: Setup menu
7.8.1 Setting Ac Voltage Alarms
1. Select AC VOLT:
[Main Menu > SETUP > (password) > ALARM SET]
1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------
Figure 119: Alarm setup menu
2. Select Set AC High & Low Alarm Levels:
[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT]
1> SET AC HIGH & LOW ALARM LEVELS
2> SET AC ALARMS HYSTERESIS
PLEASE SELECT 1
Figure 120: Ac alarms menu
3. Use the arrow keys to update values and press Ent:
[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT > Set AC High & Low
Alarm Levels]
AC VOLT SETUP: NOMINAL 220/230 VAC
---- AC ALARM SETUP ----
AC-LOW AC-HIGH
185V 286V
Figure 121: Set ac alarm voltage levels