7.12.5 Setting Power Factor Correction
1. Select Powr.Calib:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
Figure 246: Service menu
2. Enable or disable power factor correction by using the ▲▼arrow keys and Ent::
[Main Menu > SETUP > (password) > Ent > Service > Configure > Powr.Calib]
-- Set power correction factor value --
Current Value: 01%
Value to modify: 02%
------ Use Up/down, Enter Or Esc ------
Figure 247: Enabling/disabling power factor correction
7.12.6 Setting the SC2012
1. Select SC2012:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
Figure 248: Service menu
2. Select Restart controller:
[Main Menu > SETUP > (password) > Ent > Service > SC2012]
1> Restart controller 3> Network…
2> Factory settings 4> Reset MBX
Your selection: 1 5> --------------
Enter if you are sure (else press Esc.!)
Figure 249: SC2012 menu
A confirmation screen appears briefly and the controller restarts.